GYCX (L) Adjustable Induction Power Frequency Series Resonan

Recommended Products
Product Details
       Technical Specifications
        Rated Output Voltage                   0~60kV(AC RMS) and below
        Output Frequency                                         50Hz
    Resonant voltage waveform         Pure sine wave, waveform distortion rate≤1.0%
        Full load working time                     Continuous working time 1min
        System quality factors                                        10 ~40
 Frequency adjustment fineness                           3000 KVA and below
      Operating Power Supply          Three Phase 380V±15%,Frequency:50Hz±5%
 
 
Series product configuration (applicable scope (AC voltage test of generator or motor with outlet voltage of 20kV and below, test frequency: 50Hz))
Model Control Panel      Regulator      Reactor Excitation Transformer Divider   Scope of application
   GYCX(L)- 200kVA/25kV  30kW   30kVA(electric) 200kVA/25kV      one set 30kVA dry   30kV Thermal Generating Unit。0.4~1.0μF。(10kV/40MW)
   GYCX(L)- 300kVA/50kV  60kW   60kVA(electric) 300kVA/50kV      one set 60kVA Oil-immersed   50kV Thermal Generating Unit。0.27~0.33μF。(20kV/300MW)
   GYCX(L)- 600kVA/50kV   60kW    60kVA(electric) 200kVA/50kV       one set 60kVA Oil-immersed   50kV Thermal Generating Unit。0.113~0.45μF。(20kV/600MW)
400kVA/50kV       one set
   GYCX(L)- 1200kVA/50kV  120kW 120kVA(induction) 200kVA/50kV      two sets 120kVA Oil-immersed   50kV Hydroelectric Generetor。0.6~1.8μF。(20kV/250MW)
800kVA/50kV       one set
   GYCX(L)- 2750kVA/55kV  300kW 300kVA(induction) 750kVA/55kV
    two sets
120kVA Oil-immersed   60kV Hydroelectric Generetor。1.6~3.3μF。(20kV/770MW)
1250kVA/55kV        one set
Note: The solution can be customized according to the parameters of the test object
 
Reference table of electric capacity of common hydraulic generators in power system
      Hydroelectric                 generator      Rated Capacity(WM)      Rated Volage(kV) Phase Capacitor(μF)
           72.5~85               10.5          0.694
           125~150                  /          1.8~1.9
              300               15.75         1.7~2.5
              400               18           2~2.5
              600                 /          2.1~2.5
 
       Product Features
1. Due to full resonance and reactive power compensation, the power of the power supply and equipment
is only less than 1/10 of the required capacity of the tested product (1 / Q10); the volume of the same
capacity is small, the weight is light, and the output capacity of the device is large and the required configuration
of the power has small capacity, low price, convenient and safe operation.
2. The series resonance is actually a current filtering circuit, so that the current passing through the tested
product is basically the fundamental current, and the waveform distortion rate (THD) of the output voltage
is extremely small, which is superior to all existing types of AC withstand voltage equipment.
3. The short circuit current after flashover or breakdown of the test product is only 1/10 or less (1 / Q) of
the test current before short circuit, which can effectively prevent the damage to the fault point after the breakdown.
4. The arc is automatically extinguished immediately after the flashover, and the resonant state is restored after
the arc is extinguished. The process of establishing the voltage is longer (seconds). It is a steady-state
establishment process. There is no worry about voltage overshoot and no microsecond-level or millisecond-level
transient resuling from the overvoltage recovery during the process.
 
 